Mts FlexTest Models 200 Manuale Utente Pagina 211

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
Vedere la pagina 210
Model 493.72 Digital I/O Board
MTS FlexTest® Models 40/60/100/200 Controller Hardware Digital I/O and Transition Boards
211
How to Change the Debounce Settings on the Model 493.72 Digital I/O Board
If necessary, install jumpers on the Model 493.72 Digital I/O board to
change the debounce time for each group of four digital inputs.
Note The board ships with no jumpers installed, which provides a default
debounce time of 20 ms for each input.
1. Locate the four jumper sockets (X2-X5) on the Model 493.72 Digital
I/O board.
Each jumper socket sets the debounce time for a group of four inputs.
2. Install jumpers to change the debounce time.
Model 493.72
Digital I/O Board
X2
X3
X4
X5
Inputs
1-4
Inputs
5-8
Inputs
9-12
Inputs
13-16
Jumper Sockets
Debounce Jumper Settings
20 ms
(default)
10 ms 1 ms 0.1ms
1
2
4
3
Vedere la pagina 210